MIC-5001 5kV Class Insulation Tester
MIC-5001 5kV Class Insulation Tester
Price: $1995
Description
Technical specification
Files
  • Description

    Insulation resistance measurement in a compact, light-weight, low-cost design.

    • Measurement to 5 TΩ
    • Measuring voltage selectable from 50 V to 500 V range in 50 V steps, and from 500 V to 5000 V range in 100 V steps
    • Continuous indication of insulation resistance or leakage current
    • Automatic discharge of stored charge due to capacitance of tested object after the insulation resistance measurement
    • Audio beeps every five seconds to alert user test is proceeding, and to get time characteristics
    • Measured test times of T1, T2 and T3 for measuring Absorption Coefficient, Dielectric Absorption Ratio DAR. and Polarization Index PI
    • Continuous display of test voltage during the measurement
    • Protection against measuring live objects
    • Two and three-lead measurement method
    • Ramp Test Insulation resistance measurement
    • Measurement of breakdown voltage with increments up to 1 kV / s
    • Measurement of alternating and direct voltages from 0 V to 750 V 
    • 990 cells of memory (11880 records) to record results
    • Data transfer to PC via USB cable
    • Built-in rechargeable battery pack
    • Meets the requirements of the EN 61557 standard
    • Charge from optional car lighter (12 V) socket accessory
  • Technical specification

    Insulation resistance measurement (two-lead)
    Measurement range acc. to IEC 61557- 2 for RISOmin=VISOnom/IISOmax...1 TΩ (IISOmax=1 mA)

     

    Range Resolution Accuracy
    0.0 to 999.9 kΩ 0.1 kΩ ±(3% m.v. + 20 digits)
    1.000 to 9.999 MΩ 0.001 MΩ
    10.00 to 99.99 MΩ 0.01 MΩ
    100.0 to 999.9 MΩ 0.1 MΩ
    1.000 to 9.999 GΩ 0.001 GΩ
    10.00 to 99.99 GΩ 0.01 GΩ
    100.0 to 999.9 GΩ 0.1 GΩ
    1.000 to 5.000 TΩ 1 GΩ ±(4% m.v. + 50 digits)

    Values of measured resistance depending on measurement voltage

    Voltage VISO Measurement range
    up to 100 V 50 GΩ
    200 to 400 V 100 GΩ
    500 to 900 V 250 GΩ
    1000 to 2400 V 500 GΩ
    2500 V 1000 GΩ
    5000 V 5 TΩ

     

    RampTest Insulation resistance measurement

    Range Resolution Accuracy
    0.0 to 999.9 kΩ 0.1 kΩ ±(5% m.v. + 40 digits)
    1.000 to 9.999 MΩ 0.001 MΩ
    10.00 to 99.99 MΩ 0.01 MΩ
    100.0 to 999.9 MΩ 0.1 MΩ
    1.000 to 9.999 GΩ 0.001 GΩ
    10.00 to 99.99 GΩ 0.01 GΩ
    100.0 to 999.9 GΩ 0.1 GΩ
    1.000 to 4.999 TΩ 0.001 TΩ

    The measurement of breakdown voltage in RampTest mode

    Range Resolution Chosen UISO Accuracy
    25.0 V to 99.0 V 0.1 V <600 V ± 5% m.v. ± 10 digits
    100 V to 600 V 1 V <600 V ± 5% m.v. ± 4 digits
    25 V to 999 V 1 V >600 V ± 5% m.v. ± 5 digits
    1.00 kV to 5.00 kV 10V >600 V ± 5% m.v. ± 4 digits

    DC and AC voltage measurement

    Range Resolution Accuracy
    0 to 299.9 V 0.1 V ±(3% m.v. + 2 digits)
    300 to 750 V 1 V ±(3% m.v. + 2 digits)
    • frequency range: 45 to 65 Hz

    VISO - measurement voltage
    The acronym "m.v.” stands for a "measured reference value”

    Electrical safety:

    • type of insulation double, in acc. with EN 61010-1 and IEC 61557
    • measurement category IV 600 V (III 1000 V) in acc. EN 61010-1
    • case protection rating in acc. EN 60529 IP6529: IP65

    Other technical specifications::

    • power supply of the meter NiMH 9.6 V - 2 Ah battery pack and power supply 12 V
    • weight of the meter approx. 0.9 kg, 2 lbs
    • dimensions 200 x 180 x 77 mm, 7.9 x 7 x 3 ins
    • LCD segment display
    • memory for measurement results:  990 cells, 11880 records
    • transfer of measurement results data via USB